multimod-F - reactive current compensation modules in rack-mounted design

KBR detuned reactive current compensation modules in rack-mounted design

detuned reactive current compensation modules in rack-mounted design

multimod-F compensation modules in rack-mounted design are suitable for building compensation facilities in existing cabinets and are available for all cabinet systems on the market.

Highlights

  • Power from 10 to 100 kvar
  • Inductor factors 5.5, 7 or 8 % and 12.5 or 14 %
  • Capacitor rated voltage with 440 V or 525 V
  • For cabinet widths of 600 or 800 mm
  • For cabinet depths of 400, 500 or 600 mm

Technical data

Device type

GH p = 5.5, 7 or 8 %

Rated voltage | frequency:

Un = 400 V | 50 Hz
Maximum permissible operating voltage: Un = 400 V ± 10 %
Maximum permissible operating current: 1,2 x In permanently
Switching element: Capacitor contactors
Control voltage: Capacitor contactors

 >>> Control voltage transformer required for deviating operating voltage

Switching delay: 60 s
Capacitors:
Low-loss multicond-UHPC power capacitors, MTK technology
Capacitor rated voltage:
Urated = 440 V
Discharge of capacitors:
Discharge resistors t < 60 s, optional discharge inductors t < 3 s
Filter circuit inductors: Linear filter circuit inductors to avoid resonances in networks with harmonics,
integrated temperature monitoring
Inductor factors: p = 5.5, 7 or 8 %
Module version:
Module plates galvanized
Protection type:
IP 00, the components used correspond to BGV-A2
Ambient temperatures:
+ 40 °C highest value, briefly
+ 35 °C in 24-hour average
+ 20 °C in annual average
– 10 °C lowest value
Fuse protection:
Group fusing with NH fuses and fuse bases
(NH isolator on request)

Download

Technical details, data sheet (1,42 MB)

Reducing energy costs by reactive power compensation

"Reducing energy costs by reactive power compensation"

Components for reactive power compensation

KBR-Catalogue - Components for power compensation