multilog 3
Highlights
- Full recording of all electrical parameters
- Long-term and online measurements can be performed simultaneously
- Simple and quick setup without a computer
- Voltage quality assessment in accordance with EN50160 and IEC61000-2-2
- Extensive assessment functions
- Convenient graphical and tabular representation of measurement results
- Company and project details on every printout
Technical data
Measured variables and functions: | |||
---|---|---|---|
multilog 3 | Basic | Light | Expert |
Data memory in Gbyte (memory optional) | 1 | 1 | 1 |
Sampling frequency voltage | 20,48 kHz | 20,48 kHz | 20,48 kHz |
Sampling frequency current | 20,48 kHz | 20,48 kHz | 20,48 kHz |
Input voltage (resolution) | 4 (16-bit) | 4 (16-bit) | 4 (16-bit) |
Input current (resolution) | 4 (16-bit) | 4 (16-bit) | 4 (16-bit) |
Bridging energy failure | 1,5 h | 1,5 h | 1,5 h |
IP protection | IP65 | IP65 | IP65 |
Evaluation according to: EN50160 (2016) / IEC 61000-2-2 (2018) / IEC 61000-2-12 / IEC 61000-2-4 (Class 1; 2; 3) / NRS048 /IEEE 519/VDE AR-4105 |
— | yes | yes |
Recording free interval 1 sec to 30 min: | yes | yes | yes |
Recording 200 ms interval & 3 sec interval parallel to free interval | — | — | yes |
Voltage, Current: ½ periode min. max. average | yes | yes | yes |
Power: P, Q, S, PF, cos(φ), sin(φ), tan(φ) | yes | yes | yes |
Distortion-, fundamental reactive-, modulation- and unbalance power | yes | yes | yes |
Energy: P, Q, P+, P-, Q+, Q- | yes | yes | yes |
Flicker (Pst, Plt, Pinst) | — | yes | yes |
Unbalanced voltage, current; positive sequence/ negative sequence | — | yes | yes |
Voltage harmonics according IEC 61000-4-30 Ed. 3 Class A - to 50.. | — | yes | yes |
Voltage harmonics extreme values 2. to 50. (200 ms RMS) | — | — | yes |
Phase angle of voltage and current harmonics | — | — | yes |
Current harmonics 2. to 50. | — | yes | yes |
Current harmonics extreme values 2. to 50. (200 ms RMS) | — | — | yes |
Phase angle of current harmonics according fundamental of voltage | — | — | yes |
THD U and I ; PWHD U and I ; PHC | yes | yes | yes |
Frequency spectrum with 5 Hz resolution up to | — | — | 10 kHz |
Ripple control signal 100 Hz to 5 kHz (200 ms RMS max value) | — | — | yes |
Frequency, 10 sec, average-. min.- max-value | yes | yes | yes |
10/15/30 min interval P, Q, S, D, cos(φ), sin(φ), tan(φ) add to other interval | yes | yes | yes |
Online mode | |||
Oscilloscope recorder - sampling frequency | 20,48 kHz | 20,48 kHz | 20,48 kHz |
Power triangle 3D of active-, reactive, apparent power and distortion | yes | yes | yes |
Online spectrum analysis | — | — | DC bis10 kHz |
Direction of harmonics and phase angle of current harmonics | — | — | yes |
Triggerfunctions (Oscilloscope & ½ Periode RMS recorder) | |||
RMS level trigger (U, I) | — | — | yes |
RMS jump trigger (U, I) | — | — | yes |
½ periode frequency trigger (level; df/dt) | — | — | yes |
Phase shift triggerr | — | — | yes |
Envelope triggerr | — | — | yes |
Interval-trigger, automatic trigger | — | — | yes |
Option R1, Ripple signal voltage and current recorder 100 Hz to 3 kHz | RI | RI | RI |
Option S1, WLAN / Wifi interface | yes | yes | yes |
Ordering details / upgrades
- multilog 3 - basic
- multilog 3 - expert
- Upgrade of version light to expert
Current clamps:
ROGOWSKI coils
Model | Pro-Flex 3000 Set of 4 | Pro-Flex 6000 Set of 4 |
---|---|---|
Current range: | 3.000 A AC RMS | 6.000 A AC RMS |
Measuring range | 0 - 3300 A AC RMS | 0 - 6600 A AC RMS |
Output voltage: | 85 mV / 1000 A | 42,5 mV / 1000 A |
Frequenzy range: | 1 Hz to 10 kHz | 10 Hz to 10 kHz |
Operating voltage: | 600 V AC / DC CAT IV | 600 V AC / DC CAT IV |
Accuracy (20°; 50 Hz): |
-<50 A / 0,1% v.E. -50 - 3000 A / 1,5% v.M. |
-<100 A / 0,1% v.E. -100 - 6000 A / 1,5% v.M. |
(45-65 Hz): | -<50 A / 2,5° -50 - 3000 A / 1° |
-<100 A / 2,5° -100 - 6000 A / 1° |
Position accuracy: | -<50 A / 0,2% v.E. -50 - 3000 A / 1,5% v.M. |
-<100 A / 0,1% v.E. -100 - 6000 A / 1% v.M. |
Length of Rogowski coil: | 610 mm | 910 mm |
Length of connection cable: | 2 m | 2 m |
AC/DC CURRENT CLAMP (switchable)
The current clamp makes it possible to measure direct and alternating current.
Therefore, it is suitable for measurements of battery charge and intermediate direct current circuits.
60 A measuring range | |
---|---|
Current range: | 60 A AC/DC RMS |
Measuring range: | 200 mA to 60 A RMS |
Output voltage: | 10 mV / A |
Frequency range: | DC bis 10 kHz |
Accuracy: | ||
---|---|---|
Current 0-65 Hz | 0,5...40 A | 40...60 A (only for DC) |
Deviation | <1,5 % + 5 mV | <1,5 % |
Current 45...65 Hz | 10...20 A | 20...40 A |
Phase errors | <3° | <2,2° |
600 A measuring range | |
---|---|
Current range: | 600 A AC/DC RMS |
Measuring range: | >0,5mA to 600 A RMS |
Output voltage: | 1mV / A |
Frequency range: | DC bis 10kHz |
Accuracy: | |||
---|---|---|---|
Current 0-65 Hz | 0,5...100 A | 100...400 A | 400..600 A (only for DC) |
Deviation | <1,5 % + 1 mV | <2 % | <2,5% |
Current 45...65 Hz | 10...300 A | 300...400 A | |
Phase errors | <2,2° | <1,5° |
ADAPTER SET FOR EXTERNAL CURRENT CLAMPS
The free adapter set can be used to connect any other current clamps.
SWITCHABLE MINI CURRENT CLAMP 20/200A
The current clamp is particularly suitable for measurement at secondary converters in medium voltage or high voltage networks.
It offers high accuracy as well as small angle error.
20 A measuring range | |
---|---|
Current range: | 20 A AC RMS |
Measuring range: | 100 mA to 20 A RMS |
Output voltage: | 10 mV / A |
Frequency range:: | 40 Hz bis 5 kHz |
Operating voltage: | 600 V AC / DC |
Accuracy: | |||
---|---|---|---|
Current 50 Hz | 100 mA - 10 A | >10 A - 20 A | >20 A |
Accuracy | 1,5% v. M | 1% v. M | 0,5% v. M |
Angle error | 0,5° | 0,5° | 0,5° |
200 A measuring range | |
---|---|
This measuring range has to be forwarded to the network analyzer. The box is preset for the 20A measuring range of the mini current clamps. All values deviating from this ratio have to be corrected with the conversion factor of the measuring device. For the 200 A measuring range, adjust the factor x10 in the network analyzer. |
|
Current range: | 200 A AC RMS |
Measuring range: | 5 A to 200 A RMS |
Output voltage: | 1 mV / A |
Frequency range: | 40 Hz to 10 kHz |
Operating voltage: | 600 V AC / DC |
Accuracy: | |||
---|---|---|---|
Current 50 Hz | >10 A - 40 A | >40 A - 100 A | >100 A - 200 A |
Accuracy | <2 % v. M | <1,5 % v. M | <1 % v. M |
Angle error | <2° | <1,5° | <1° |