Three-phase network measuring instrument
multimess D4 is a multimeter for DIN rail mounting. As a competitively priced output-side measuring device, it can measure all typical alternating and direct current parameters of consumers. You can connect the optional multimess F96-DS display with a ready-made RJ12 cable. This way, no complicated wiring of the voltage and, most importantly, current path from the transformer to the door is necessary. Up to 10 measuring modules can be read out and displayed. Connection between the modules is also established via ready-made RJ12 cables. Power supply of the measuring device is provided by the measuring voltage. A separate control voltage is not necessary. If the multimess D4 is connected to the multisio D6 instead of to the display, the former serves as a load profi le memory (P+ -/ Q+ Q-) and an eBus interface. Five measuring modules can be connected to each central storage module.
Highlight
- Cost-efficient multimeter for mounting rail installation
- No additional supply voltage necessary
- No transformer cables to switchgear cabinet necessary
- Up to 10 measuring modules per display
- Network capable for application with multisio central module
Technical Data
Combination Possibilities:
Device Type: | ||
---|---|---|
multimess D4-BS mit multimess F96-DS1 |
multimess D4-BS mit multisys D2-BSES |
multimess D4-BS mit multisio D6 und multisio F96-DS |
LCD display 96 x 96 | ||
Standard | - | Standard |
Number of measuring modules | ||
10 per display | no limit | 5 per multisio D6 |
eBus | ||
- | Standard | Standard |
eBus TCP | ||
- | Standard2 | Standard3 |
Instantaneaous value display | ||
Standard | - | Standard |
Display eBus | ||
- | Standard | Standard |
Load profile memory | ||
- | - | - |
Display eBus | ||
- | Standard4 | Standard |
Contonous counter value | ||
Standard | - | Standrad |
Display eBus | ||
- | Standard4 | Standard |
1 For energy supply of the display, an additional power supply unit, e.g. multisys D4-P-24V is required
2 For application of multisys D2-BSET gateway instead of D2-BSES
3 Additional gateway multisys D2-ESET required
4 In connection with visual energy 4, daily consumption values are created automatically.
15-min-period values are supplementary values (daily consumption / 96)
Downloads
multimess - Energy measuring devices (10194 KB)
User manual - Technical parameters (826 KB)