Overview switching group
There are 255 switch groups per location:
- Switch groups 1 - 200 are freely available to the user.
- Switch groups 201 - 255 are used for system error messages..
You can assign any number of free eBus device relays to switch groups. Switch groups are assigned in the respective device properties. Different actions are applied to the switch groups with different priorities. For example, a manual switching operation has a higher priority than a system action.
Description | Priority |
---|---|
Maunal switching | 1 |
Timer programs | 2 |
Dvice/system action | 3 |
Alarm groups
Gruppe | Verwendung | Hinweis |
---|---|---|
255 | Collective fault horn |
Switches at 250 |
254 |
Collective fault indicator |
Switches at 250 |
253 |
Collective warning horn |
Switches at 240 |
252 |
Collective warning indicator |
Switches at 240 |
250 |
Collective fault |
Switches at 249, 245, 244, 243 |
249 |
Collective fault network |
Switches at 248, 247, 246, 245 |
248 |
|
|
247 |
|
|
246 |
Collective fault power supply |
|
245 |
Collective fault network miscellaneous |
|
244 |
Collective fault limit violation |
|
243 |
Collective fault device problem |
|
240 |
Collective warning |
Switches at 239, 238, 237, 236, 235 |
239 |
||
238 |
||
237 |
||
236 |
Collective warning network miscellaneous |
|
235 |
Collective warning device warnings |