Reactive power compensation directly at the source

multicab-F - Fixed capacitors

Reactive power compensation components
multicab F 050 01 1000 14 SWGH

The multicab-F fixed capacitors compensate the inductive reactive power directly at the point of origin.

The great advantage of fixed capacitors is that they significantly reduce the load on the supply lines to the consumers. Fixed capacitors are used for loads with relatively high power, such as transformers and motors.

In the standard version, you receive the fixed capacitors in a sheet steel wall cabinet according to your requirements.

Highlights
Technical data

DIMENSIONS (H x W x D in mm):

S2 (800 x 800 x 400)

S3 (1200 x 800 x 400)

  • Outputs from 5 to 60 kvar
  • Throttling factors 5.5, 7 or 8 % or 12.5 or 14 %
  • Capacitor rated voltage with 440 V or 525 V
  • Optional: power contactor and NH isolator

Device type: multicab-F – fixed capacitor

SWSH p = 5.5, 7 or 8 %
SWSB p = 12.5 or 14 %
Rated voltage | frequency: Un = 400 V | 50 Hz
Maximum permissible operating voltage: Un = 400 V ± 10 %
Maximum permissible operating current: 1.3 xIn permanent
Capacitors: Low-loss multicond UHPC power capacitors, MTK technology
Nominal capacitor voltage: Umeasurement = 440 V, Umeasurement = 525 V
Discharge of the capacitors: Discharge resistors t < 180 s, optional discharge chokes t < 3 s
Filter circuit chokes: Linear filter circuit chokes to avoid resonances in networks with harmonics, built-in temperature monitoring
Throttling factors: p=5.5,7 or 8 %, p=12.5 or 14 %
Housing design: Sheet steel enclosure, interior and exterior paint finish RAL 7035 (other paint finishes on request), galvanized modular panels
Protection class: IP 20 (IP 54 on request), the components used comply with DGUV regulation 3
Ambient temperature: + 40 °C maximum, short-term + 35 °C 24-hour average + 20 °C annual average – 10 °C minimum
Option: Additional NH protection: with NH isolator and NH fuses
Option: Additional LS switching element: Capacitor contactorsUSteuer = 230 V, 50 Hz, control voltage transformer
Required for different operating voltage
Option: Apparent current relay additional LSR: Apparent current relay Additional LSR, connection and disconnection via line contactor
>>> Control voltage transformer required for deviating operating voltage
Switching delay: 180 s
Fittingly:
Tablet mit Screenshot

Download

More information (brochures, user manuals, etc.) under download.