Reactive power compensation in the floor-standing cabinet

Compensation system multicab-R-S

Reactive power compensation systems

Floor cabinet

Highlights
Technical details

DIMENSIONS (H x W x D in mm):

S4 (2000 x 800 x 400)
S5 (2000 x 800 x 600)

  • Outputs from 75 to 400 kvar
  • Throttling factors 5.5, 7 or 8 % or 12.5 or 14 %
  • Capacitors multicond-UHPC with 440 V or 525 V
  • Reactive power controller multicomp D6 LCD with display
  • Simple system expansion thanks to push-insert technology
  • Optional: security and maintenance concept secureC ©

Device type

SSGH p = 5.5, 7 or 8 %
SSGB p = 12.5 or 14 %
Rated voltage | frequency: Un = 400 V | 50 Hz
Maximum permissible operating voltage: Un = 400 V ± 10 %
Maximum permissible operating current: 1.3 xIn permanent
Reactive power controller: multicomp D6 with display
4-quadrant operation
Optimized control behavior
Circuit switching
Current transformer connection: Optionally available
Switching element: Capacitor contactors
Control voltage: Utax = 230 V, 50 Hz
>>> Control voltage transformer required for deviating operating voltage
Switching delay: 180 s
Capacitors: Low-loss multicond UHPC power capacitors, MTK technology
Nominal capacitor voltage: UBem. = 440 V (SWSH); UBem. = 525 V v(SWSB)
Discharge of the capacitors: Discharge resistors t < 180 s Optional discharge chokes t < 3 s
Filter circuit chokes: Linear filter circuit chokes to avoid resonances in networks with harmonics,
Built-in temperature monitoring
Throttling factors: p = 5.5, 7 or 8 % (SWSH); p = 12.5 or 14 % (SWSB)
Housing design: Sheet steel cabinet, interior and exterior paint finish RAL 7035 (other paint finishes on request),
Galvanized module panels, door hinge left (optionally right), bottom feed (on request from above), protection class I
Protection class: IP 20 (IP 54 on request), the components used comply with DGUV regulation 3 (on EN “DGUV rule 3”)
Ambient temperatures: + 40 °C Maximum value, short-term
+ 35 °C in 24-hour average
+ 20 °C annual average
– 10 °C Lowest value
Ventilation: Built-in roof ventilator, temperature-controlled
Protection: Group fuse protection with NH fuses and fuse bases
(NH isolator on request)
montage_loeschpatrone-halterung-rauchmelder_de_

Other safety components

secure-c_

Safety and maintenance module

multicab-r_thyro_open-closed-multicomp_

Compensation system with thyristors

KBR
Support Team

We are happy to arrange
the contact to our
references and are available for
available for an interview.

Just get in touch with us.
Phone: +49 9122 6373-0
E-mail: info@kbr.de