multict ECTB

Bushing type current transformers for billing purposes - screwless connection

Measure, Current transformer

multict ECTB

The current transformers for internal billing purposes from the multict ECTB series are suited for use in conjunction with an MID energy consumption meter.

The current transformer’s calibration period is indefinite.

 

Conformity

The conformity of transformers is documented by a yellow conformity mark and a declaration of conformity enclosed with the product.

 

Quality assurance

The quality assurance system must be recognized by the PTB in accordance with module D of the conformity evaluation procedure, so that billing transformers can be used directly for billing purposes. For other European countries, these design-approved current transformers are approved for billing purposes.

 

The current transformers from the multict ETCB series are also set apart by the “Cage Clamp®” screwless connection technology.

The springless connection technology with spring terminal makes connections gas-tight and maintenance-free. Thanks to the strong retaining forces, the current transformer can be used even in conditions of high mechanical stress (e.g. vibrations). The spring terminal is 2 designed for solid and flexible conductors up to a max. of 4 mm². This eliminates the need for ferrules.

Billing current transformers for current ranges from 25 A to 3,000 A in accuracy classes 0.2s, 0.2, 0.5s, 0.5.

 

Application

Establishing a measuring point, which is consulted for billing.

Highlights
Technical Data
More information

With PTB type approval for setting up a measuring point, which is required for billing.

Bushing type current transformer, screwless connection “Cage Clamp” for billing purposes – multict ECTB

 

  • All types with PTB design approval
  • Calibrated version orderable
  • Primary rated current 100 A – 2000 A
  • class 0.2s, 0.2, 0.5s, or 0.5
  • Requires no maintenance thanks to screwless technology

 

Maximum operating voltage Um 1.2 kV
Rated continuous thermal current Icth 1.2 x In
Rated short-time thermal current Ith 60 x In , 1sec (max. 100 kA)
Rated surge current Idyn 2.5 x Ith
Overcurrent limiting factor FS 5
Rated frequency 50 Hz
Insulation class E
Insulation test voltages 6 kV, 1 min, Ueff , 50 Hz (Um ≤ 1.2 kV)
Working temperature range –5°C ≤ T ≤ +50°C
Storage temperature range –25°C ≤ T ≤ +70°C
Applied norms DIN EN 61869/1+2, DIN 42600-1, DIN 42600-2
Unbreakable plastic housing made of polycarbonate
Flame-resistant and self-extinguishing in accordance with UL 94
Nickel-plated secondary clamps with plus/minus screws (2 Nm)

Schraubenlose Anschlusstechnik dank Federzugklemme „Cage Clamp®“

 

All devices are delivered including the the materials necessary for fastening.

Included in the scope of delivery:

  • 1 primary rail clamp
  • 2 screws M5x35
  • 2 secondary terminal covers
  • 2 mounting feet

 

CAUTION: If a cable lug is already pressed on the cable, it must be considered when determining the window size of the transformer.

Fittingly:
Gruppenbild der multimess Energiemessgeräte

KBR
Support Team

We are happy to arrange
the contact to our
references and are available for
available for an interview.

Just get in touch with us.
Phone: +49 9122 6373-0