All-rounder measuring device with LED display

multimess F144 LED

Measure, Energy measuring devices
Measuring accuracy
nach DIN EN 61557-12
Voltage quality
according to DIN EN 61000-4-30 Possible interfaces: KBR eBus*, Modbus*,
Profibus*, KBR eBus TCP*,
Modbus TCP* *depending on the respective device type [1]-[4], [6]-[8] are also available with NRTL certification.
multimess F144 0 xxx 5 NRTL

The 3-phase network measuring devices from the multimess F144-LED series measure and monitor all important variables in the three-phase three-phase network and are available in a wide range of performance classes.

The load profile of the measured system can be saved for up to 366 days with a 15-minute measurement period. The integrated event memory logs up to 1500 events, such as: E.g. limit violations, power failures, voltage drops and much more.

Highlights
Technical data
Metrics/memory
Connection diagrams
  • Measuring accuracy according to DIN EN 61557-12
  • Power quality according to DIN EN 61000-4-30
  • Separate current transformer input for neutral conductor current
  • PE leakage current is displayed
  • Many performance classes for every area of application
  • Extensive displays, functions and storage options
  • Optimum readability thanks to bright LED displays
  • Variety of inputs and outputs (digital/analog)
  • Low installation depth of just 60 mm

multimess F144 power meter

Device types overview
Article no.
US1
Article no.
US5
(optional)
Article no.
US1-NRTL
[1] multimess F144-0-LED-EP-2RO1DO-US_ 24007 24008 24014
[2] multimess F144-2-LED-ESMS-2RO1DO-US_ 23654 23659 23883
[3] multimess F144-2-LED-ESMSET-2RO1DO-US_ 23655 23660 23884
[4] multimess F144-2-LED-ESMSMT-2RO1DO-US_ 23656 23661 23885
[5] multimess F144-2-LED-ESMSDP-2RO1DO-US_ 23657 23662
[6] multimess F144-2-LED-ESMS-2RO1DO3AO-US_ 22809 23666 23886
[7] multimess F144-2-LED-ESMSET-2RO1DO3AO-US_ 23663 23667 23887
[8] multimess F144-2-LED-ESMSMT-2RO1DO3AO-US_ 23664 23668 23888
[9] multimess F144-2-LED-ESMSDP-2RO1DO3AO-US_ 23665 23669

US1: 100 bis240 V +/- 10% AC/DC 50/60 Hz, 18 VA, 10 W
US5 (optional): 22,5 bis 64 V +/- 10% AC/DC 50/60 Hz, 15 VA, 10 W

Input and output configuration
Device types [1] [2] [3] [4] [5] [6] [7] [8] [9]
Digital inputs
1 synchronization,
1 HT/NT tariff
Yes Yes Yes Yes Yes Yes Yes Yes
Pulse output (P+/Q+) 1
Pulse output (P+/Q+/P-/Q-)
1

1

1

1

1

1

1

1

Relay output 21 21, 2 21, 2 21, 2 21, 2 21, 2 21, 2 21, 2 21, 2
Analog outputs 3 3 3 3
Interface RS485 RS485 RS485 RS485 RS485 RS485 RS485 RS485
KBR eBus Yes Yes Yes Yes Yes Yes Yes Yes
KBR eBus TCP Yes Yes
Modbus RTU/ASCII Yes Yes Yes Yes Yes Yes Yes Yes
Modbus-TCP Yes Yes
Profibus-DP Yes Yes
Power supply US1: 100 bis240 V +/- 10% AC/DC 50/60 Hz, 18 VA, 10 W
US5 (optional): 22,5 bis 64 V +/- 10% AC/DC 50/60 Hz, 15 VA, 10 W

1 Limit function
2 Additional switching reality function via bus

Details, metrics and storage – [1]

Details, metrics and storage
multimess F144-0-LED-…

[1] …EP-2RO1DO-US_

Metrics
Tension U Ph–N (L1 – L3) | U Ph-Ph
Electricity I Ph (L1 – L3)
Average current value I Ph (L1 – L3)
Neutral conductor current IN | IN means
Apparent power S Ph (L1 – L3) | S total
Active power P Ph (L1 – L3) | P total
Q1 = fundamental reactive power Q1 (L1 – L3) | Q 1 total
Frequency f network
Harmonics THD (L1 – L3) voltage
Rotating field control: rotating field display in degrees Yes
Performance factors Fundamental oscillation cosφ (L1 – L3)
Total power factor λ (L1 – L3) | λ total
Electrical work Endless counter for active work P+
Endless counter for blind work Q+
Tariff switchable HT / NT
Memory
Load profile memory P total / Q total
Storage duration of the load profiles
(with a 15 minute measurement period)
Daytime, active and blind work
Split pointer function (min. / max.) For all displayed measured values, Wir-2 and reactive power period 2 with date and time
Event memory
Operational diary


2
Maximum value only

Details, metrics and storage – Device type[2]to[9]

Details, metrics and storage
multimess F144-2-LED-…

[2] …ESMS-2RO1DO-US_
[3] …ESMSET-2RO1DO-US_
[4] …ESMSMT-2RO1DO-US_
[5] …ESMSDP-2RO1DO-US_

multimess F144-2-LED-… (with 3 analog outputs)

[6] …ESMS-2RO1DO3AO-US_
[7] …ESMSET-2RO1DO3AO-US_
[8] …ESMSMT-2RO1DO3AO-US_
[9] …ESMSDP-2RO1DO3AO-US_

Metrics
Tension U Ph–N (L1 – L3) | U Ph-Ph
Electricity I Ph (L1 – L3)
Average current value I Ph (L1 – L3)
Neutral conductor current IN | IN-average
Apparent power S Ph (L1 – L3) | S total
Active power P Ph (L1 – L3) | P total
Q1 = fundamental reactive power Q1 (L1 – L3) | Q 1 total
Frequency f network
Harmonics THD (L1 – L3) voltage
THD (L1 – L3) current
3rd – 63th Harm. (L1 – L3) Tension
3rd – 63th Harm. (L1 – L3) Electricity
Rotating field control: rotating field display in degrees Yes
Performance factors Fundamental oscillation cosφ (L1 – L3)
Total power factor λ (L1 – L3) | λ total
Electrical work Endless counter for active work P+ | P-
Endless counter for blind work Q+ | Q-
Tariff switchable HT / NT
Memory
Load profile memory P total / Q total P+1 | Q+1 (cumulative)
P-1 | Q-1 (cumulative)
Storage duration of the load profiles
(with a 15 minute measurement period)
Ring memory for 366 days
Daytime, active and blind work Annual working memory, daily values for active and reactive work 1
Split pointer function (min. / max.) For all displayed measured values, Wir-2 and reactive power period 2 with date and time
Event memory 1500 events with date, time and duration, e.g. Limit values exceeded and undershot, power failures and voltage increases ≥ 20 ms at 100% measurement voltage drop 1
Operational diary 500 entries with date and time 1

 

1 Only available via the interface

2 Maximum value only

Connection diagram – [1]

 

Connection diagram Anschlussplan multimess F144 0 LEDxxx 5 TYP 1


Connection diagram – [2] bis [9]

 

Connection diagram Anschlussplan multimess F144 2 LEDxxx 5 TYP 2 bis 9

Fittingly: