Display |
Operation |
Push button for reset and scan mode |
Display |
5 LEDs:
2x input status
2x initial state
1x Operating status |
Temperature input |
PT 1000 |
1 |
Outputs |
Relay contact, potential-free (common source),
Switching capacity 250 V AC, 2A |
2 potential-free, separate relays |
Interface |
KBR eBUS (RS485) |
– |
KBR module bus (RS485) |
Standard |
Baud rate |
38400 |
Addressing |
Automatic module bus addressing, scan mode can be activated on the device |
Power supply |
Operating voltage |
24 V DC, supply via module bus |
Power consumption |
1 VA |
Mechanical data |
Housing dividing units
and size in mm (HxWxD) |
2 TE (90 x 35 x 61) |
Mounting type |
Wall mounting on standard rail
7.5 mm deep, in accordance with DIN EN 50022,
Suitable for manifold installation |
Weight |
approx. 80 g |