Search
Storage center for the multisio system

multisio D6

Signal acquisition and processing
multisio D6 multisio TFT Buehne
Display
multisio F96-TFT
Storage center
multisio D6-ESBSDS-5DI6RO1DO

multisio D6 is the storage center for the modular system for signal recording and processing. Depending on the input or output type, a variety of functions can be selected.

The system is able to record the pulses from consumption meters and store them both as continuous meter data and as standard load protocols. Alternatively, a digital input can also be used to record the status (switching protocol) or the operating hours. Operating hours are available as continuous meter data and graphs. Compact expansion modules are available for a wide variety of signal forms (0 – 20 mA, 4 – 20 mA, 0 – 10 V, PT1000, current, power, etc.). Up to four expansion modules can be connected to each system control center using pre-assembled RJ45 cables.

Highlights
Techn. Data multisio D6
Techn. Data display
  • Ideal for use in installation distribution boards
  • Compact design
  • Can be expanded modularly
  • Large selection of modules for digital and analog inputs/outputs as well as for temperature recording

 

Input and output configuration
Inputs Outputs Possible functions
5x digital 6x relays Consumption recording
1x DO Status logging
1x Display Operating hours recording
Pulse summation
Relay circuit
Analog value acquisition
Temperature detection
Heat quantity recording
Electrical work
Type:
multisio D6-ESBSDS-5DI6RO1DO-7 Article no. 20221
multisio D6-ESBSDS-5DI6RO1DO-7 NRTL Article no. 24439

 

Control and display elements:
Operation Push button for reset and scan mode
Display LED: 5 x input status, 1 x operating status,
multisio F96-DS (LCD)

 

Storage:
Working, data and parameter memory 2 MB Flash
Program memory 512 kB Flash
Memory type Ring buffer
Extreme values (max./min.) The maximum values that have occurred since mains connection or manual extreme value deletion (drag indicator function) with date and time
Event event memory Storage amount 1500 events with 1500 events with the date and time they occurred
Operational diary Storage amount 500 entries with 500 entries with the date and time of their occurrence
Limit violation Capture time ≥ 200 ms
Voltage dips in the measurement voltage Capture time ≥ 20 ms; Threshold adjustable via PC, ≥ 20 ms; Threshold adjustable via PC, default after reset 85% of the nominal voltage (according to EN61000-4-30)

 

Power supply:
Power supply US1: 100 – 240 V ±10% DC/50/60 Hz
Power consumption 22 VA

 

Hardware inputs:
Digital inputs As pulse counter input 1 to 5 Digital input for potential-free contact, S0 – compatible, pulse length ≥ 30ms
As a status input Digital input for potential-free contact, S0 – compatible, e.g. B. to synchronize the measurement period; Pulse length ≥ 250 ms
Voltage-voltage supply 27 V / 15 m A DC supplied internally

 

Electrical connection:
Connecting elements Plug-in terminals
Max. permissible cross section of the connecting cables 2,5 mm2
Input power supply Validation max. 1A sluggish
max. C2 Automatic machine
Mains isolating device approved to UL/IEC
KBR eBus connection Connecting material For correct operation, only use shielded and twisted pair cables; e.g. I-Y(St)Y 2x2x0.8
Pulse inputs Wiring & cables pay attention to correct polarity!
Synchronous input Wiring & cables pay attention to correct polarity!
KBR eBus connection via RS485 Terminal 90 (⊥)
Terminal 91 (A)
Terminal 92 (B)

 

Hardware outputs:
Interfaces Serial interface RS 485 for connection to the KBR eBus; Max. 32 devices per bus segment, up to 1000 m without a bus amplifier if installed appropriately, for further information see the KBR eBus installation guidelines
Transfer speed 38400 baud
Bus protocol KBR eBus
KBR eBus addressing Addressable up to address. 9999 via software, scan mode can be activated on the device
Module bus interface Serial interface RS 485 (RJ12) for assembled KBR system cable (6-pole modular cable, not shielded), max. length 30 m when laid appropriately.
Display- und Konfigurationsschnittstelle Serial interface RS485 (RJ12)
Relay outputs Switching steps 5 relays
Switching performance 250 V (AC) / 2A per relay, potential depends on the common connection – not touch-proof
Fault signal relay Switching performance 250 V (AC) / 2 A potential-free – not safe to touch

 

Mechanical data:
DIN rail device Housing dimensions 90 x 106 x 61 mm (H x W x D)
Mounting type Wall mounting on standard rail 7.5 mm deep, in accordance with DIN EN 50022
Weight approx. 650g

 

Environmental conditions / electrical safety:
DIN rail device Standards DIN EN 60721-3-3/A2: 1997-07; 3K5+3Z11; (IEC721-3-3; 3K5+3Z11)
Operating temperature K55 (-5°C …. +55°C)
Air humidity 5 % … 95 %, non-condensing
Storage temperature K55 (-25°C …. +70°C)
Operating height 0…2000 m above sea level
Electrical safety Standards DIN EN 61010-1: 2011-07
Protection class I
Overvoltage category CAT III
Rated impulse voltage 4 kV
Protection class Standards IP20 according to DIN EN 60529: 2014-09
EMC Standards DIN EN 61000-6-2:2006-03 + Corrigendum 1:2011-03
DIN EN 61000-6-3:2011-09 + Corrigendum 1:2012-11
DIN EN 61326-1:2013-07
Power supply:
Power supply ext. 24 VDC, 1 W, via RJ12 module bus connector

 

Hardware inputs and outputs:
Serial interface Module bus RS485 via RJ12 socket
Baud rate 38400

 

Electrical connection:
Module bus – connection Connecting material Assembled KBR system cable (modular cable 6-pin, not shielded), max. length 30m when laid appropriately

 

Mechanical data:
Panel device Housing dimensions 96 x 96 x 46 mm (H x W x D)
Installation cutout 92 x 92 mm
Protection class Front IP 40
Weight approx. 175 g

 

Environmental conditions / electrical safety:
Ambient conditions Standards DIN EN 60721-3-3/A2: 1997-07; 3K5+3Z11; (IEC721-3-3; 3K5+3Z11)
Operating temperature K55 (-5°C …. +55°C)
Air humidity 5 % … 95 %, non-condensing
Storage temperature K55 (-25°C …. +70°C)
Operating height 0…2000 m above sea level
Electrical safety (in conjunction with the basic device) Standards DIN EN 61010-1: 2011-07
Protection class I
Overvoltage category CAT III
Rated impulse voltage 4 kV
Protection class Standards IP20 according to DIN EN 60529: 2014-09
EMC Standards DIN EN 61000-6-2:2006-03 + Corrigendum 1:2011-03
DIN EN 61000-6-3:2011-09 + Corrigendum 1:2012-11
DIN EN 61326-1:2013-07
Fittingly: